AIR VELOCITY SENSORS

Applications & Features
It is designed for air velocity monitoring and controlling in the ventilation
system and reducing energy consumption in BMS and various HVAC
application. It is applied for single point air velocity measurement. SAVTD is for duct mount, SAVTR is for remote installation
Based on thermal anemometer principle, use innovative and sensitive hot film sensor, which is insensitive to dust and dirt, easy to install and maintain
No moving parts, provide accurate, reliable, sensitive and long term measurement, with good temp. compensation
Multiple outputs, ranges and optional LCD display
Specification
Air velocity sensor: Hot film sensor
Range: 0~5/10/15/20m/s or 0~16/32/48/64ft/s, jumper selectable
Accuracy: m/s: ±±(0.2m/s+5% reading) or ±±(0.2m/s+3% reading)
@0.5~20m/s; ft/s: ±±(0.65ft/s +5% reading) or ±±(0.65ft/s +3%
reading) @1.6~64ft/s 25 C, 55%RH, 1013hPa
Response time: typical 2s
Angle dependence: < 3%reading @ | Δα | < 10
Temperature compensation: 10~40 C
Temp. output(option): range 0~50 C, accuracy < 0.5 C@25 C
Output: 4~20mA (3 wires), 0~10/0~5VDC, RS485/Modbus
Output Load: ≤500Ω(current), ≥2kΩ(voltage)
Display: LCD, with unit m/s or ft/s, DIP switch selectable
Power: 16~28VAC/16~35VDC
Working Environment: 20~70 C, 0~95%RH (Non cond.)
Housing: fire retardant PC (UL94 V 0)
Protection: IP65
Weight: 440g
Approval: CE